Duct Size Calculator
Find the round or rectangular duct size for an airflow and friction rate, or check the friction and velocity of a duct you have.
- Exact diameter
- Velocity
- Friction
- Rectangular option
- Area
- Next Standard Size
Duct Schedule
Items you add are saved in this browser.
| Run | CFM | Size | FPM | In./100 Ft. | Remove |
|---|
How to Size a Duct
The equal friction method picks a pressure loss per 100 feet of duct and sizes every run to it. The standard duct friction chart for galvanized steel duct can be written as a formula, which this page solves for the diameter.
The rectangular equivalent (Huebscher's formula) gives the round diameter with the same friction and airflow as an a × b rectangular duct.
Worked Example
Round Duct Capacity at 0.08 In. per 100 Ft.
| Diameter | CFM | Velocity (FPM) |
|---|
Tips
The formula fits smooth galvanized sheet metal duct. Flex duct has far more friction, often double or more when it's compressed or sags, so size it larger. Residential supply branches are usually kept under about 700 to 900 FPM to stay quiet. For a full design, ACCA Manual D ties duct sizes to the blower's available static pressure.